6 Vector Control and Applied Functions
6 - 60
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter
No.
Function name
Data
Default
data
Unit
H103
PM Motor Capacity
0.1/0.2/0.4/0.55/0.75/1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5
Maximum
applicable
motor
capacity
kW
H104
PM Motor Pole
Number
2/4/6/8
10 to 48: Do not set.
Dependent
on capacity
pole
A003
1st Base Frequency
30.0 to 1st Maximum Frequency (A004)
60.0
Hz
A004
1st Maximum Fre-
quency
1st Base Frequency (A003) to 400.0
60.0
Hz
A082
1st Motor Rated
Voltage Selection
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
200 or 400
V
H105
PM Motor Rated
Current
0.20 Rated current to 1.00 Rated current
Rated
current
A
b012
1st Electronic Ther-
mal Level
0.20 Rated current to 1.00 Rated current
Rated
current
A
H109
PM motor Parame-
ter Ke
0.0001 to 6.5535
Dependent
on capacity
Vp/
(rad/s)
H110
PM motor Parame-
ter J
0.001 to 9999.000
*1
Dependent
on capacity
kgm
2
A051
DC Injection Brak-
ing Selection
00: Disabled
01: Enabled
02: Enabled (Operates only at set frequency)
00
b033
Motor Cable Length
5. to 20.
10.
m
Parameter
No.
Function name
Data
Default
data
Unit
H001
Auto-tuning Selec-
tion
00: Disabled
01: Enabled (No motor rotation)
00