Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1) 
 
 
 
 
 
⚫
 
Connection diagram for commercial switching operation 
 
MC2 
 
 
⚫
 
Timing diagram for commercial switching 
 
 
 
MC1 
 
 
MC2 
MC3 
FW input 
(FWY) 
CS input 
(CSY) 
 
 
Motor 
rotation speed 
 
 
Output 
frequency 
 
Driven
 
by
 
commercial
 
power
 
supply
 
Switching
 
from
 
inverter
 
Operation
 
to
 
Co
 
mmercial
 
Power
 
Supply
 
Operation
 
Switching from Commercial Power Supply Operation to inverter Operation 
 
• 
Make sure that MC3 and MC2 are mechanically interlocked. Doing so may cause an inverter dam- 
age. 
 
 
  Additional Information 
 
• 
For FWY, RVY, and CSY, use low-voltage relays according to your application. 
• 
If an overcurrent trip occurs during frequency pull-in restart, increase the Restart Standby 
Time (b003). 
• 
The inverter can be set up to restart automatically at power-on. In this case, the terminal CS 
is not required. For details, refer to 5-8-2 Restart after Resetting on page 5-44. 
 
Interlock time for MC2 and 
Inverter power supply ON 
Inverter power supply OFF
 
Interlock time for MC2 and MC3 
Switching between commercial power 
supply and motor disconnection 
7-5  Other Operation Functions 
7-5-14  Commercial Switching (CS)