In the Power Interruption/Undervoltage Trip Selection During Stop (b004), select whether or not to have 
the inverter output an alarm signal if a power interruption or undervoltage occurs. 
The inverter will output an alarm signal as long as its control power supply remains ON. 
 
⚫
 
Alarm signal output in case of power interruption/undervoltage during stop 
(Example 1) b004 = 00 (Disabled) 
 
Power supply 
 
RUN command 
 
 
Output frequency 
 
 
AL output 
(Alarm signal) 
RS input (Reset) 
 
 
(Example 2) b004 = 01 (Enabled) 
 
Power supply 
RUN command 
 
Output frequency 
 
 
AL output 
(Alarm signal) 
RS input (Reset) 
 
 
(Example 3) b004 = 02 (Disabled during stop and during deceleration by RUN command OFF) 
 
Power supply 
 
RUN command 
 
 
Output frequency 
 
 
AL output 
(Alarm signal) 
RS input (Reset)