7 Other Functions
7 - 76
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
7-8 Functions Related to Protection, Warning, and Various Output Signals
7-8-2 Motor Electronic Thermal Function
Parameter
No.
Function name
Data
Default
data
Unit
b012/b212
1st/2nd Electronic Thermal
Level
0.20 Rated current to 1.00 Rated current
Rated
current
A
b013/b213
1st/2nd Electronic Thermal
Characteristics Selection
00: Reduced torque characteristics
01: Constant torque characteristics
02: Free setting
01
b910
Motor Electronic Thermal
Selection
*1*2
00: Disabled
01: Enabled (Fixed subtraction rate)
02: Enabled (b911 subtraction rate)
03: Enabled (b912 time parameter subtraction)
03
b911
Motor Electronic Thermal
Subtraction Ratio
0.10 to 100000.00
*3
(Displays upper 5 digits)
600.00
s
b912
Motor Electronic Thermal
Subtraction Time Constant
0.10 to 100000.00
*3
(Displays upper 5 digits)
120.00
s
b913
Motor Electronic Thermal
Integration Gain
1.0 to 200.0
100.0
%
b914
Electronic Thermal Load
Rate Memory Selection at
Power-off
00: Disabled
01: Enabled
01