Loading...
8 Communications Functions
8 - 69
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1380
hex
137F hex
Brake Release
Frequency
b125
R/W
0 to 59000
0.01
[Hz]
P. 6-25
1381
hex
1380 hex
Brake Release
Current
b126
R/W
0 to 2000
0.1 [%]
1382
hex
1381 hex
Brake Force
Frequency
b127
R/W
0 to 59000
0.01
[Hz]
1383
hex
Reserved
1384
hex
1385
hex
1384 hex
Overvoltage
Suppression
Function Selection
During Deceleration
b130
R/W
00: Disabled
01: DC voltage kept con-
stant
02: Acceleration enabled
P. 5-62
1386
hex
1385 hex
Overvoltage
Suppression Level
During Deceleration
b131
R/W
200-V class:
330 to 400
400-V class:
660 to 800
1 [V]
1387
hex
1386 hex
Overvoltage
Suppression
Parameter During
Deceleration
b132
R/W
10 to 3000
0.01 [s]
P. 5-62
1388
hex
1387 hex
Overvoltage
Suppression
Proportional Gain
During Deceleration
b133
R/W
0 to 500
0.01
1389
hex
1388 hex
Overvoltage
Suppression Integral
Time During
Deceleration
b134
R/W
0 to 1500
0.1 [s]
138A to
1393
hex
Reserved
1394
hex
1393 hex
GS Input Operation
Selection
b145
R/W
00: Not trip
01: Trip
P. 7-103
1395 to
13A5
hex
Reserved
13A6
hex
13A5 hex
d001/d007 Data
Setting Selection
b163
R/W
00: Disabled
01: Enabled
P. 7-4
P. 7-6
13A7
hex
13A6 hex
Initial Screen
Automatic Return
Function
b164
R/W
00: Disabled
01: Enabled
P. 7-56
13A8
hex
13A7 hex
Operation Selection
at External Operator
Disconnection
b165
R/W
00: Trip
01: Trip after deceleration
stop
02: Ignore
03: Free-run stop
04: Deceleration stop
P. 7-56