8 Communications Functions
8 - 77
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
143A
hex
1439 hex
Overtorque/
Undertorque
Selection
C054
R/W
00: Overtorque
01: Undertorque
P. 6-15
143B
hex
143A hex
Overtorque/
Undertorque Level
(Forward Power
Running)
C055
R/W
0 to 200
1 [%]
143C
hex
143B hex
Overtorque/
Undertorque Level
(Reverse
Regeneration)
C056
R/W
0 to 200
1 [%]
143D
hex
143C hex
Overtorque/
Undertorque Level
(Reverse Power
Running)
C057
R/W
0 to 200
1 [%]
143E
hex
143D hex
Overtorque/
Undertorque Level
(Forward
Regeneration)
C058
R/W
0 to 200
1 [%]
143F
hex
143E hex
Overtorque/
Undertorque Signal
Operation
C059
R/W
00: Enabled during
acceleration/decel-
eration and con-
stant speed
01: Enabled during
constant speed
1440
hex
Reserved
1441
hex
1440 hex
Electronic Thermal
Warning Level
C061
R/W
0 to 100
1 [%]
P. 7-77
1442
hex
Reserved
1443
hex
1442 hex
0 Hz Detection Level
C063
R/W
0 to 10000
0.01
[Hz]
P. 5-57
1444
hex
1443 hex
Cooling Fin Over-
heat Warning Level
C064
R/W
0 to 110
1 [°C]
P. 7-88
1445 to
144A
hex
Reserved
144B
hex
144A hex
Communication
Speed Selection
(Baud Rate
Selection)
C071
R/W
03 (2400 bps)
04 (4800 bps)
05 (9600 bps)
06 (19.2 kbps)
07 (38.4 kbps)
08 (57.6 kbps)
09 (76.8 kbps)
10 (115.2 kbps)
P. 8-5
144C
hex
144B hex
Communication Sta-
tion No. Selection
C072
R/W
1 to 247
144D
hex
Reserved
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List

Table of Contents