EasyManua.ls Logo

Omron 3G3MX2-A2002-EV2 - Page 529

Omron 3G3MX2-A2002-EV2
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Communications Functions
8 - 85
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1610
hex
Reserved
1611
hex
1610 hex
Positioning
Completion Range
Setting
P017
R/W
0 to 10000
1
[pulse]
P. 6-34
1612
to
1619
hex
Reserved
161A
hex
1619 hex
Overspeed Error
Detection Level
P026
R/W
0 to 1500
0.1 [%]
P. 6-23
161B
hex
161A hex
Speed Deviation
Excessive Level
P027
R/W
0 to 12000
0.01
[Hz]
161C to
161E
hex
Reserved
161F
hex
161E hex
Acceleration/
Deceleration Time
Input Type
P031
R/W
00: Digital Operator
03: DriveProgramming
P. 5-32
1620
hex
Reserved
1621
hex
1620 hex
Torque Reference
Input Selection
P033
R/W
00: Terminal O
01: Terminal OI
03: Digital Operator
06: Option (No applica-
ble Option)
P. 6-16
1622
hex
1621 hex
Torque Reference
Setting
P034
R/W
0 to 200
1 [%]
1623
hex
Reserved
1624
hex
1623 hex
Torque Bias Selec-
tion
P036
R/W
00: Disabled
01: Digital Operator
05: Option (No applica-
ble Option)
P. 6-17
1625
hex
1624 hex
Torque Bias Value
P037
R/W
200 to 200
1 [%]
1626
hex
1625 hex
Torque Bias Polarity
Selection
P038
R/W
00: As per sign
01: Dependent on
RUN direction
1627
hex
Reserved
1628
hex
1627 hex
Speed Limit Value in
Torque Control
(Forward)
P039
R/W
0 to 12000
0.01
[Hz]
P. 6-16
1629
hex
Reserved
162A
hex
1629 hex
Speed Limit Value in
Torque Control
(Reverse)
P040
R/W
0 to 12000
0.01
[Hz]
P. 6-16
162B
hex
162A hex
Speed/Torque
Switching Time
P041
R/W
0 to 1000
1 [ms]
162C to
1638
hex
Reserved
8
8-9 Modbus Communication Data Lists
8-9-4 Group A/b/C/H/P Register List

Table of Contents

Related product manuals