EasyManua.ls Logo

Omron 3G3MX2-A2002-EV2 - Page 538

Omron 3G3MX2-A2002-EV2
612 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Communications Functions
8 - 94
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
16E7
hex
16E6 hex
Modbus Mapping
Internal Register 1
P301
R/W
0000 to FFFF hex
1
P. 8-24
16E8
hex
16E7 hex
Modbus Mapping
Internal Register 2
P302
R/W
0000 to FFFF hex
1
16E9
hex
16E8 hex
Modbus Mapping
Internal Register 3
P303
R/W
0000 to FFFF hex
1
16EA
hex
16E9 hex
Modbus Mapping
Internal Register 4
P304
R/W
0000 to FFFF hex
1
16EB
hex
16EA hex
Modbus Mapping
Internal Register 5
P305
R/W
0000 to FFFF hex
1
16EC
hex
16EB hex
Modbus Mapping
Internal Register 6
P306
R/W
0000 to FFFF hex
1
16ED
hex
16EC hex
Modbus Mapping
Internal Register 7
P307
R/W
0000 to FFFF hex
1
16EE
hex
16ED hex
Modbus Mapping
Internal Register 8
P308
R/W
0000 to FFFF hex
1
16EF
hex
16EE hex
Modbus Mapping
Internal Register 9
P309
R/W
0000 to FFFF hex
1
16F0
hex
16EF hex
Modbus Mapping
Internal Register 10
P310
R/W
0000 to FFFF hex
1
16F1
hex
16F0 hex
Modbus Mapping
Endian Selection
P400
R/W
00: Big endian
01: Little endian
02: Special endian
P. 8-29
16F2 to
1E00
hex
Not used
Not accessible

Table of Contents