1 Overview
1 - 42
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
b092
3G3MX2-E
3G3MX2-EV2
00: Disabled
Constant operation
Constant operation
01: Enabled only during
operation
It operates under the following conditions.
During operation (Stops 5 minutes after
operation stop)
For 5 minutes after power-on
It operates under the following conditions.
During operation (Stops if fin tempera-
ture falls below 50°C for 3 minutes after
operation stop)
Even while stopped, if fin temperature
exceeds 60°C (Stops if fin temperature
falls below 50°C for 3 minutes)
02: Dependent on
cooling fin temperature
It operates under the following conditions.
Cooling fin temperature of approxi-
mately 45°C or higher (Stops when it
falls below 45°C)
It operates under the following conditions.
Cooling fin temperature of approximately
40°C or higher (Stops if fin temperature
falls below 40°C for 3 minutes)
Alarm
code
Description
3G3MX2-E
3G3MX2-EV2
E08.
EEPROM error
Yes
Yes
E10.
Current detector error
Yes
E11.
CPU error
Yes
Yes
E14.
Ground protection
Yes
Yes
E22.
CPU communications error
Yes
E25.
Main circuit error
Yes
E30.
Driver error
Yes
OFF/ON Operation of Cooling Fan
1
1-5 Comparison with Previous
Model
1-3-2 External Dimensions
Changes in Output Targets for Fatal Fault Signal (MJA) of
Multi-function Output

Table of Contents

Related product manuals