EasyManua.ls Logo

Omron CJ - REFERENCE MANUAL 07-2009

Omron CJ - REFERENCE MANUAL 07-2009
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
147
C-mode Command Details Section 4-3
Response Format
Limitations The data is read in the same order in which it was registered with QQMR.
Execution Conditions
End Codes An end code of 14 (format error) will be returned if the length of the command
is incorrect.
An end code of 19 (not executable) will be returned if there is no registered
data.
4-3-37 ABORT – – XZ
Aborts the Host Link command that is currently being processed, allowing the
next command to be received.
Command Format
Limitations Multiple responses to a command can be cancelled with this command.
An FCS code and terminator are required.
End Codes
The ABORT command does not receive a response.
,
@QQ
x 10
0
x 10
1
x 16
1
x 16
0
I R
x 16
3
x 16
2
x 16
1
x 16
0
*
ON/
OFF
x 10
3
x 10
2
x 10
1
x 10
0
ON/
OFF
Unit No.
(BCD)
Header code
End code
Timer/counter word designation:
ON: 1; OFF: 0 + word data (BCD)
Data break
Bit data
ON/OFF
Word data
CIO, LR, AR, HR, WR,
DM, EM and other word
(Hex) data.
TerminatorFCS
,,
,
Commands Responses PLC Mode UM Area
Single Multiple Single Multiple RUN MON PROG Write-protected Read-protected
OK No OK OK OK OK OK OK OK
End code (Hex) Contents
00 Normal completion
13 FCS error
14 Format error
18 Frame length error
19 Not executable
21 Not executable due to CPU Unit CPU error.
@ X Z
x 10
0
x 10
1
*
Unit No. (BCD)
Header
code
TerminatorFCS

Table of Contents

Related product manuals