42
Settings for Sending FINS Commands Section 3-4
3-4-4 CMND(490) Setting Example
The designated number of bytes of FINS command data from the first com-
mand word designated by operand S is sent to the designated unit address
via the node address on the network address designated by operand C, and
the response is stored for the number of bytes of data received starting from
D.
In this example, a command (MEMORY AREA READ: 0101 Hex) for reading
D00010 to D00019 of the PLC at node 02 is sent using CMND(490).
D00010: Memory area code (82 Hex), address 000A00
Number of elements read: 10 = 0A Hex
S: First command word
D: First response word
C: First control word
S: First command word
C: First control word
Command code
Beginning read address
Memory area code
Beginning read address
Number of elements read
D: First response word
Control code
End code
Read data
Read data
Number of command data bytes
Number of response data bytes
Destination network address
Destination unit address
Destination node address
Communications port number
Number of retries
Response required/not required
Response monitor time
Serial port No.
0000
0000
0002
0300
0000
0101
0082
0A 00
0A00
0101
0800
1800