157
Command Lists Section 5-1
10: Command
format error
01: Command
too long
Command data The command is longer than
the maximum permissible
length.
Check the command format and
correct the command data.
02: Command
too short
Command data The command is shorter than
the minimum permissible
length.
Check the command format and
correct the command data.
03: Elements/
data don’t
match
Command data The designated number of
elements differs from the
number of write data items.
Check the number of elements and
set data for each element.
04: Command
format error
Command data An incorrect format was
used.
Check the command format and
correct the command data.
05: Header
error
Routing table Either the relay table in the
local node or the local net-
work table in the relay node is
incorrect.
Set the routing tables correctly.
11: Parameter
error
01: Area classi-
fication missing
Memory area
code in
command data
The specified word does not
exist in the memory area or
there is no EM Area.
Check the memory areas and
parameter codes in the command
and correct the command data.
02: Access size
error
Access size
specification in
command data
The access size specifica-
tion is incorrect or an odd
word address is specified.
Check the memory areas and
access size and correct the access
size.
03: Address
range error
Starting address
in command data
The start address in com-
mand process is beyond the
accessible area.
Check the area being processed
and set the correct range.
04: Address
range
exceeded
Starting address
and number of
elements in
command data
The end address in com-
mand process is beyond the
accessible area.
Check the area being processed
and set the correct range.
Data link tables The total number of words is
beyond the limit.
Correct the data link tables.
06: Program
missing
Program
number in
command data
FFFF hex was not specified. Specify FFFF hex.
09: Relational
error
Command data A large–small relationship in
the elements in the command
data is incorrect.
Check the command data and
correct the relationship between the
elements.
Data link table A node not set in the
common link parameters is
set as a refresh parameter.
Correct the data link tables.
0A: Duplicate
data access
I/O access in
CPU Unit
Differential monitoring was
specified during data tracing
or data tracing was specified
during differential monitoring.
Abort the current process or wait
until it ends before executing the
command
.
Data link tables The same node address is
specified more than once.
Correct the data link tables.
0B: Response
too long
Number of ele-
ments in com-
mand data
The response format is
longer than the maximum
permissible length.
Check the command format and
correct the number of elements.
0C: Parameter
error
Parameters in
command data
There is an error in one of the
parameter settings.
Check the command data and
correct the parameters.
Data link table
file
There is an error in the file. Check the contents of the file.
Main code Sub-code Check point Probable cause Correction