EasyManuals Logo

Omron M1 Series User Manual

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #276 background imageLoading...
Page #276 background image
Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
C37
Input Terminal [AI2]
Gain AII Com-
mand
0.00 to 400.00 %
100.00
Availa-
ble
%
page
7-38
page
7-123
C38
Input Terminal [AI2]
Filter (AII)
0.00 to 5.00 s
0.05
Availa-
ble
s
page
7-123
C39
Input Terminal [AI2]
Gain (AII Analog In-
put)
0.00 to 100.00 %
100.00
Availa-
ble
%
page
7-38
page
7-123
C40
Input Terminal [AI2]
Operation Selection
(AII)
0: 4 to 20mA Unipolar
1: 0 to 20mA Unipolar
10: 4 to 20mA Bipolar
11: 0 to 20mA Bipolar
0 -
-
page
7-38
page
7-123
C41
Input Terminal [AI2]
Offset AIV
-5.0 to 5.0 %
0.0
Availa-
ble
%
page
7-38
page
7-123
C42
Input Terminal [AI2]
Gain (AIV Command)
0.00 to 400.00 %
100.00
Availa-
ble
%
page
7-38
page
7-123
C43
Input Terminal [AI2]
Filter (AIV)
0.00 to 5.00 s
0.05
Availa-
ble
s
page
7-123
C44
Input Terminal [AI2]
Gain (AIV Analog In-
put)
0.00 to 100.00 %
100.00
Availa-
ble
%
page
7-38
page
7-123
C45
Input Terminal [AI2]
Polarity Selection
(AIV)
0: Bipolar
1: Unipolar
1 - -
page
7-38
page
7-123
C50
Input Terminal [AI1,
AI2] Bias Analog Input
for 1st Frequency
Command
0.00 to 100.00 %
0.00
Availa-
ble
%
page
7-38
C53
Input Terminal [AI1,
AI2] Normal/Inverse
Operation for 1st Fre-
quency Command
0: Normal
1: Inverse
0
Availa-
ble
-
page
7-44
4 Parameter List
4-110
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C