Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H15
Continuous Running
V
oltage Level
200 to 300 V (200 V class ser-
ies)
400 to 600 V (400 V class ser-
ies)
235
Availa-
ble
V
page
7-49
H16
Allowable Time for
Power Interruption Re-
start
0.0 to 30.0 s
999: Auto judgment
32767
Availa-
ble
s
page
7-49
H18
Torque Control Oper-
ate Selection
0: Disable (Speed control)
2: Torque current command in-
put
3: Torque command input
0
- -
page
6-31
H26
Thermistor Function
Selection (MOH)
0: Disable
1: PTC (Inverter immediately
trips with OH4 displayed)
2: PTC (Inverter issues output
signal MOH and continues to
run)
0
Availa-
ble
-
page
7-88
H27
1st Thermistor Error
Detection Level
(MOH)
0.00 to 5.00 V
1.60
Availa-
ble
V
page
7-88
H28 Droop Control
-60.0 to 0.0 Hz
0
Availa-
ble
Hz
page
7-149
H42
Main Circuit Capacitor
Service Life Coef
fi-
cient (Measurement
Value)
0: Start measurement
1: Measurement failure
2 to 65535: Measurement val-
ue
0
Availa-
ble
-
page
7-96
H43
Cumulative Run Time
of Cooling Fan
0 to 9,999 (in 10 hours)
0
Availa-
ble
10
hex
page
7-99
H44
1st Startup Count for
Motor
0 to 65,535
0
Availa-
ble
-
page
7-93