Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H60
S-curve Deceleration
Range Frequency at
End
0 to 100 %
10
Availa-
ble
%
page
5-40
H61
UP/DOWN Control Ini-
tial Value Selection
0: 0.00Hz
1: Last UP/DOWN command
value
1 - -
page
7-119
H63
Frequency Lower Limit
Operation Selection
0: Frequency Command is the
Frequency Lower Limit.
1: Frequency Command is
0Hz
0
Availa-
ble
-
page
5-32
H64
Low Frequency during
Protecting Overload
0.0: Depends on Frequency
Lower Limit(F16)
0.1 to 590.0 Hz
1.6
Availa-
ble
Hz
page
7-82
H67
Auto Energy Saving
Operation Condition
Selection
0: Enable only at constant
speed
1: Enable in all modes
0
Availa-
ble
-
page
7-141
H68
1st Slip Compensation
Operating Conditions
Selection
0: Enable during acceleration/
deceleration, enable at base
frequency or higher
1: Disable during acceleration/
deceleration, enable at base
frequency or higher
2: Enable during acceleration/
deceleration, disable at base
frequency or higher
3: Disable during acceleration/
deceleration, disable at base
frequency or higher
0 - -
page
5-16
4 Parameter List
4-120
M1 Series Standard Type User's Manual (I669)