Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H69
Anti-regenerative Con-
trol Function Selection
0: Disable
2: Torque limit control with
forced stop after three times
deceleration time has passed
3: Main Circuit DC Voltage
control with forced stop after
three times deceleration time
has passed
4: T
orque limit control without
forced stop
5: Main Circuit DC Voltage
control without force-to-stop
0
Availa-
ble
-
page
7-85
H70
Overload Prevention
Control
0.00: Depend on selected de-
celeration time
0.01 to 100.00 Hz/s
999: Cancel
32767
Availa-
ble
Hz/s
page
7-82
H71
Over-Excitation Con-
trol Selection during
Deceleration Function
Selection
0: Disable
1: Enable
0
Availa-
ble
-
page
7-121
H72 Do not use - - - - -
H74
Torque Limit Function
Selection
0: Torque limit
1: Torque current limit
1 -
-
page
6-81
H75
Torque Limit Operation
Selection
0: Four quadrants independent
1: Four quadrants identical
0 - -
page
6-81
H76
Frequency Rising Lim-
it for T
orque Limit
0.0 to 590.0 Hz
5
Availa-
ble
Hz
page
6-81
H77
Service Life of Main
Circuit Capacitor Re-
maining Time
0 to 8760 (in 10 hours)
8760
Availa-
ble
10
hex
page
7-96
H78
1st Motor Mainte-
nance Interval
0: Disable
1 to 9999 (in 10 hours)
8760
Availa-
ble
10
hex
page
7-93
4 Parameter List
4-121
M1 Series Standard Type User's Manual (I669)
4-2 List of Parameters by Group
4
4-2-5 Parameter H (High Level Functions)