Parameter
No.
Function name Monitor or Data Range
Default
data
Setting
during
RUN
Unit Page
H79
1st Preset Startup
Count for Motor Main-
tenance
0: Disable
1 to 65,535
0
Availa-
ble
-
page
7-93
H80
1st Output Current
Fluctuation Damping
Gain
0.00 to 1.00
0.20
Availa-
ble
-
page
7-144
H81
Light Alarm Selection
1
0000 to FFFF Hex
0
Availa-
ble
-
page
7-108
H82
Light Alarm Selection
2
0000 to FFFF Hex
0
Availa-
ble
-
page
7-108
H84 Pre-excitation Level
100 to 400 %
100
Availa-
ble
%
page
7-151
H85 Pre-excitation Timer
0.00: Disable
0.01 to 30.00 s
0.00
Availa-
ble
s
page
7-151
H86 Do not use - - - - -
H89
Motor Electronic Ther-
mal Overload Protec-
tion Data Retention
0: Disable
1: Enable
1
Availa-
ble
-
page
5-20
H90 Do not use - - - - -
H91
Current Input Wire
Break Detection
0.0: Disable alarm detection
0.1 to 60.0 s: Issue alarm after
set time
0
Availa-
ble
s
page
7-123
H92
Continuous Running
at the Momentary
Power Failure P Pro-
portional Gain
0.000 to 10.000
999: Auto
32767
Availa-
ble
-
page
7-49
H93
Continuous Running
at the Momentary
Power Failure Integral
Time
0.010 to 10.000 s
999: Auto
32767
Availa-
ble
s
page
7-49
4 Parameter List
4-122
M1 Series Standard Type User's Manual (I669)