EasyManua.ls Logo

Omron R88A-MCW151-DRT-E - Page 40

Omron R88A-MCW151-DRT-E
276 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
Components and Unit Settings Section 2-1
DeviceNet (MCW151-DRT-E only)
Switch Settings
The MCW151 Units are equipped with the following DIP-switches.
DeviceNet Switch Settings (MCW151-DRT-E only)
The external switch settings will set the Slaves node address setting and
baud rate setting.
Node address
The node address of the slave is set with pins 1 through 6 of the DIP switch.
Any node address within the setting range can be used as long as it is not
already set on another node.
Indi
ca-
tor
Color Status Definition Meaning
MS Green ON Device
Operational
Normal operating status.
Flashing Device in
Standby
Reading switch settings.
Red ON Unrecover-
able Fault
Unit hardware error: Watchdog timer error.
Flashing Minor Fault Switch settings incorrect.
--- OFF No Unit
Power
Unit power is not supplied, waiting for initial
processing to start, or the Unit is being reset.
NS Green ON Link OK.
Online, Con-
nected.
Network is operating normally (communica-
tions established).
Flashing Online, Not
connected
Network is operating normally, but communi-
cations have not yet been established.
Red ON Critical Link
Failure
A fatal communications error has occurred.
Network communications are not possible.
Flashing Connection
Timeout
Communications timeout.
--- OFF No Fieldbus
Power / Not
Online
Checking for node address duplication on the
Master, switch settings are incorrect, or field-
bus power is not supplied.
1 2
3
4
56
7
8910
ON
1 NA0
NA1
2
NA2
3
NA3
4
NA4
5
NA5
6
MD0
7
NC
8
DR0
9
DR1
10
ON

Table of Contents

Related product manuals