8-4 Analog Control Parameters
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
8
Parameters Details
Select the speed limit.
The speed limit is used as a protection during torque control.
Refer to "5-3 Torque Control (P.5-6)".
Explanation of Set Values
Set the speed limit value for torque control.
It controls that the speed during torque control does not exceed the set value.
Refer to "5-3 Torque Control (P.5-6)".
Pn315
Unused
Setting
range
Unit
Default
setting
Data
attribute
Pn316
Unused
Setting
range
Unit
Default
setting
Data
attribute
Pn317
Speed Limit Selection
Setting
range
0 to 1 Unit
Default
setting
0
Data
attribute
B
Set value Description
0 Select the value set on the Speed Limit Value Setting (Pn321).
1
Select either the speed limit value (VLIM) via MECHATROLINK-II communications
or the value set by the Speed Limit Value Setting (Pn321), whichever is smaller.