6-3
Note The carrier frequency changes as shown in the following graph with 7 through 9 set in n46.
Carrier Frequency (n46: 7 through 9)
Carrier
Frequency
83.3 Hz (Set value: 7)
41.6 Hz (Set value: 8)
27.7 Hz (Set value: 9)
208.3 Hz (Set value: 7)
104.1 Hz (Set value: 8)
69.4 Hz (Set value: 9)
Output frequency
The Inverter cannot maintain rated output current with the carrier frequency set to a value higher than
the default one.
The following table shows the default value and a decrease in the output current of each Inverter mod-
el.
Be sure to use the Inverter so that there will be no decrease in rated output current.
Voltage Model 3G3JV- Default setting Rated output
current (A)
Set to 3
Reduced rated
output current
(A)
Set to 4
Reduced rated
output current
(A)
3-phase
200 V
A2001 4 (10 kHz) 0.8
p
200 V
A2002 4 (10 kHz) 1.6
A2004 4 (10 kHz) 3.0
A2007 4 (10 kHz) 5.0
A2015 3 (7.5 kHz) 8.0 7.0
A2022 3 (7.5 kHz) 11.0 10.0
A2037 3 (7.5 kHz) 17.5 16.5
Single-phase
200 V
AB001 4 (10 kHz) 0.8
gp
200 V
AB002 4 (10 kHz) 1.6
AB004 4 (10 kHz) 3.0
AB007 4 (10 kHz) 5.0
AB015 3 (7.5 kHz) 8.0 7.0
3-phase
400 V
A4002 3 (7.5 kHz) 1.2 1.0
p
400 V
A4004 3 (7.5 kHz) 1.8 1.6
A4007 3 (7.5 kHz) 3.4 3.0
A4015 3 (7.5 kHz) 4.8 4.0
A4022 3 (7.5 kHz) 5.5 4.8
A4037 3 (7.5 kHz) 8.6 7.6
Advanced Operation Chapter 6