9-14
9-2-8 Digital Operator Connection Cable
H 3G3IV-PCN126/PCN326
The Digital Operator Connection Cable (3G3IV-PCN126/PCN326) is required to connect a Digital
Operator to a 3G3JV Inverter.
H Models and Specifications
Digital Operator Connection Cable Cable length
3G3IV-PCN126 1 m
3G3IV-PCN326 3 m
9-2-9 DC Reactor
H 3G3HV-PUZDABj
The DC Reactor suppresses harmonic current gener-
ated from the Inverter and improves the power factor of
the Inverter. The DC Reactor suppresses harmonic cur-
rent more effectively than the AC Reactor. Furthermore,
the DC Reactor can be used in combination with the AC
Reactor.
H Applicable Model
Inverter DC Reactor
Voltage
class
Max. applica-
ble motor ca-
pacity (kW)
Model Rated
voltage
(V)
Rated
current
(A)
Induc-
tance
(mH)
Loss (W)
200 V
0.1 to 0.75 3G3HV-PUZDAB5.4A8MH
800 V DC
5.4 8 8
1.5 to 3.7 3G3HV-PUZDAB18A3MH 18 3 18
400 V
0.2 to 0.75 3G3HV-PUZDAB3.2A28MH
800 V DC
3.2 28 9
1.5 to 2.2 3G3HV-PUZDAB5.7A11MH 5.7 11 11
3.7 3G3HV-PUZDAB12A6.3MH 12 6.3 16
Specifications Chapter 9