7-24
Note There is an OR relationship between input from the control terminals and input through commu-
nications, except for the RUN command and forward/reverse rotation command.
D Inverter Output (Register 0009 Hex)
Bit No. Function
0 Multi-function contact output (1: ON)
1 to 15 Not used.
Note The settings will be enabled if multi-function output n40 is set to 18 for communications output.
Then the output terminals (MA to MC) will be turned ON and OFF through communications.
H Broadcast Message with Slave Address: 00 (00 Hex) Write
Register No.
(Hex)
Function Description
0000 Not used. ---
0001 RUN command Refer to the table below.
0002 Frequency reference Set the frequency reference based on the maximum
frequency as 30,000.
0003 to 000F Not used. ---
Note 1. Data can be written to registers 0001 and 0002 only. Assumed previous values are held for
unused registers.
Note 2. No data can be written to multi-function input.
Note 3. The unit of setting of the broadcast message is different from that in the DSR message to com-
municate with a single Slave.
D RUN Command (Register 0001 Hex)
Bit No. Function
0 RUN command (1: RUN)
1 Forward/Reverse (1: Reverse)
2 to 3 Not used.
4 External fault (1: External fault EF0)
5 Fault reset (1: Fault reset)
4 to 15 Not used.
7-7-2 Monitor Functions
Register No.
(Hex)
Function Description
0020 Status signal Refer to the following corresponding table.
0021 Fault status Refer to the following corresponding table.
0022 Data link status Refer to the following corresponding table.
0023 Frequency reference According to the set value in n69.
0024 Output frequency According to the set value in n69.
0025 to 0026 Not used. ---
Communications Chapter 7