5-4
5-2 V/f Control
H Setting the V/f Patterns (n09 to n15)
• Set the V/f pattern so that the motor output torque is adjusted to the required load torque.
• The 3G3JV incorporates an automatic torque boost function. Therefore, a maximum of 150% torque
can be output at 3 Hz without changing the default settings. Check the system in trial operation and
leave the default settings as they are if no torque characteristic changes are required.
n09
Maximum Frequency (FMAX) Changes during
operation
No
Setting
range
50.0 to 400 (Hz) Unit of
setting
0.1 Hz
(See note 1.)
Default setting 60.0
n10
Maximum Voltage (VMAX) Changes during
operation
No
Setting
range
1 to 255 (V) (See note 2.) Unit of
setting
1 V Default setting 200 (See
note 2.)
n11
Maximum Voltage Frequency (FA) Changes during
operation
No
Setting
range
0.2 to 400 (Hz) Unit of
setting
0.1 Hz
(See note 1.)
Default setting 60.0
n12
Middle Output Frequency (FB) Changes during
operation
No
Setting
range
0.1 to 399 (Hz) Unit of
setting
0.1 Hz
(See note 1.)
Default setting 1.5
n13
Middle Output Frequency Voltage (VC) Changes during
operation
No
Setting
range
1 to 255 (V) (See note 2.) Unit of
setting
1 V Default setting 12 (See
note 2.)
n14
Minimum Output Frequency (FMIN) Changes during
operation
No
Setting
range
0.1 to 10.0 (Hz) Unit of
setting
0.1 Hz Default setting 1.5
n15
Minimum Output Frequency Voltage (VMIN) Changes during
operation
No
Setting
range
1 to 50 (V) (See note 2.) Unit of
setting
1 V Default setting 12 (See
note 2.)
Note 1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz incre-
ments if the frequency is 100 Hz or greater.
Basic Operation
Chapter 5