15-15
15 Troubleshooting
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
15-2 Troubleshooting
15
15-2-1 Error Table
34270000 hex Tag Name
Resolution
Error
Resolution of a tag
used in a tag data
link failed.
The size of the network variable
is different from the tag set-
tings.
The I/O direction set for a tag
data link and the I/O direction of
the Controller variable do not
match.
There are no network variables
for the Controller tag settings.
A variable in the Controller that
is set for a tag data link has the
Network Publish attribute set to
Input but also has the Constant
attribute.
S page 15-31
34280000 hex
(Ver. 1.10 or
later)
Basic Ether-
net Setting
Error
An error was
detected in the
Ethernet settings.
Parameter error
Power was interrupted when a
download was in progress for
the built-in EtherNet/IP port set-
tings.
A memory error occurred.
S page 15-32
34290000 hex
(Ver. 1.10 or
later)
IP Address
Setting Error
An error was
detected in the IP
address settings.
Parameter error
Power was interrupted when a
download was in progress for
the built-in EtherNet/IP port set-
tings.
The IP address acquired from
BOOTP server is illegal.
A memory error occurred.
S page 15-33
342A0000 hex
(Ver. 1.10 or
later)
DNS Setting
Error
An error was
detected in the
DNS settings or
Hosts settings.
Parameter error
Power was interrupted when a
download was in progress for
the built-in EtherNet/IP port set-
tings.
A memory error occurred.
S page 15-34
50010000 hex
(Ver. 1.02 or
later)
Controller
Insufficient
Memory
Warning
The amount of data
for the EtherCAT
slave configura-
tion, network-pub-
lished information,
or other data
exceeds the value
that is specified for
the CPU Unit. You
may not be able to
perform online edit-
ing or other opera-
tions.
The amount of data for the Eth-
erCAT slave configuration, net-
work-published information, or
other data exceeds the value
that is specified
for the C
PU
Unit.
S page 15-35
84030000 hex DNS Server
Connection
Error
Connection with the
DNS server failed.
Parameter error
Server is down.
An error occurred in the com-
munications path.
S page 15-36
84040000 hex NTP Server
Connection
Error
Connection with the
NTP server failed.
Parameter error
Server is down.
An error occurred in the com-
munications path.
S page 15-36
84070000 hex Tag Data Link
Connection
Failed
Establishing a tag
data link connection
failed.
The tag data link connection
information is not the same for
the originator and target.
Insufficient connections
S page 15-37
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info

Table of Contents