15 Troubleshooting
15-14
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
84010000 hex IP Address
Duplication
Error
The same IP
address is used
more than once.
The IP address of the built-in
EtherNet/IP port is also used as
the IP address of another node.
S page 15-23
84020000 hex BOOTP
Server Con-
nection Error
Connection with the
BOOTP server
failed.
Server setting error
Server is down.
An error occurred in the com-
munications path.
S page 15-24
04210000 hex
(Ver. 1.10 or
later)
Communica-
tions Control-
ler Failure
A hardware error
was detected in the
communications
controller of the
built-in EtherNet/IP
port.
Hardware error in the communi-
cations controller
S page 15-24
14210000 hex Identity Error The CIP identity
information in non-
volatile memory
was not read cor-
rectly.
Non-volatile memory failure S page 15-25
14230000 hex
(Ver. 1.10 or
later)
MAC
Address
Error
The MAC address
in non-volatile
memory was not
read correctly.
Non-volatile memory failure S page 15-25
34200000 hex Tag Data Link
Setting Error
An error was
detected in the
communications
settings for tag data
links.
Power was interrupted when a
download was in progress for
the data link settings.
Memory error
S page 15-26
34230000 hex IP Route
Table Setting
Error
An IP routing set-
ting error was
detected.
Setting error
Power was interrupted when a
download was in progress for
the built-in EtherNet/IP port set-
tings.
Memory error
S page 15-27
34240000 hex FTP Server
Setting Error
An error was
detected in the FTP
server settings.
Setting error
Power was interrupted when a
download was in progress for
the FTP server settings.
Memory error
S page 15-28
34250000 hex NTP Client
Setting Error
An error was
detected in the NTP
client settings.
Setting error
Power was interrupted when a
dow
nload was in progress for
the NTP client settings.
Memory error
S page 15-29
34260000 hex SNMP Set-
ting Error
An error was
detected in the
SNMP agent/trap
settings.
Setting error
Power was interrupted when a
download was in progress for
the SNMP agent/trap settings.
Memory error
S page 15-30