15-49
15 Troubleshooting
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
15-2 Troubleshooting
15
15-2-2 Error Descriptions
*1 This applies to an NJ-series CPU Unit.
*2 This applies to an NX-series CPU Unit.
*1 This applies to an NJ-series CPU Unit.
*2 This applies to an NX-series CPU Unit.
Event name IP Address Fixed Event code 94080000 hex
Meaning The correct IP address has been determined and Ethernet communications can start.
Source EtherNet/IP Function Module Source details Communications
port,
*1
communi-
cations port 1,
*2
or Communica-
tions port 2
*2
Detection
timing
At power ON or
Controller reset
Error attributes Level Information Recovery --- Log category System
Effects User program Continues. Operation Not affected.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
Lights. --- ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The correct IP address has been
determined and Ethernet communica-
tions can start.
--- ---
Attached
information
Attached Information 1: IP address (example: C0A8FA01 hex = address 192.168.250.1)
Precautions/
Remarks
None
Event name BOOTP Client Started Event code 94090000 hex
Meaning The BOOTP client started requesting an IP address.
Source EtherNet/IP Function Module Source details Communications
port,
*1
communi-
cations port 1,
*2
or Communica-
tions port 2
*2
Detection
timing
At power ON or
Controller reset
Error attributes Level Information Recovery --- Log category System
Effects User program Continues. Operation Not affected.
Indicators EtherNet/IP NET RUN EtherNet/IP NET ERR EtherNet/IP LINK/ACT
--- --- ---
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The BOOTP client started requesting
an IP address.
--- ---
Attached
information
None
Precautions/
Remarks
None