- 82 – Aries Controller Hardware Installation Guide
Protective Circuits
Short Circuit Protection
The Aries Controller drive has an internal circuit that protects it from short
circuits between one motor terminal to another (phase to phase), or from any
motor terminal to earth.
Short Circuit Fault—Cause .....................Phase-to-phase short circuit
Phase-to-earth short circuit
Results of Fault ....................................... Power to motor is turned off
Drive status word is updated
via Ethernet to the PC
LED Left LED Right
Yellow &
1 Green (blinking)
Red
Table 33 LED Short Circuit Fault
Resetting the fault
To clear the latched fault, choose one of the following methods:
Cycle power to the drive/controller.
–or–
Open ACR-View and issue the DRIVE RES AXIS0 command to the Aries
Controller.
Drive/Controller Over-Temperature Protection
The Aries Controller over-temperature circuit monitors the drive/controller’s
internal temperature. If the sensors exceed the threshold temperature, the
unit issues an over-temperature fault.
Threshold Temperature
AR-04CE, AR-08CE, and AR-13CE 80°C (176°F)
Results of Fault ....................................... Power to motor is turned off
Drive status word is updated
via Ethernet to the PC
LED Left LED Right
Yellow &
3 Green (blinking)
Red
Table 34 LED Drive Over-Temperature Fault