intervals). If this occurs, check all harness connectors and the fuse for proper
seating. If all connections are secure but the RMP continues to self-test, replace
the fuse with the spare included in the hardware kit.
If this does not correct the
problem, contact your local field service office for verification that the RMP is
working correctly.
6.
To test the indicator lamps, press the horn silence button and hold it for 3
seconds. All lamps should light, and the horn will sound continuously until you
release the button.
7. Repeat steps 1 through 6 for each RMP you are installing. You can install up to
two
RMPs
or
RIMS.
6.
After installing all
RMPs
or
RIMS,
secure the UPS cabinet by reversing all steps
of the procedure used to prepare the UPS (see page 19).
Powerware
Plus
80
UPS Installation Manual