‐30‐
INSERTION/EXTRACTION PROCEDURE
The following operations must only be performed by skilled and specifically trained personnel.
When the CP is not inserted, parts with voltage are present on the corresponding backplane.
Insert or remove the CP only during first installation or in the case of maintenance operations.
Strictly comply with the instructions as listed below.
EXTRACTION
Undo the two side screws.
Using the handle provided under the display,
carefully pull and remove the CP.
INSERTION
Carefully insert the CP in the dedicated slot.
Fasten the CP by fastening the two side screws
removed previously.
BATTERY UNIT (BU)
The Battery Unit (BU) contains 10 off 12V batteries (120Vdc) which can be replaced during maintenance if required.
INSERTION/EXTRACTION PROCEDURE
The following operations must only be performed by skilled and specifically trained personnel.
When the BU is not inserted, uncovered parts with dangerous voltage are present on the corresponding
backplane.
Never touch the base of the BU near the connector: a dangerous voltage is present.
The BU, due to its weight, must be handled by at least two persons.
Strictly comply with the instructions as listed below.