EasyManua.ls Logo

Rockwell Automation 5094-IA16 - FLEX 5000 I;O Safety Output Module Safety Data

Rockwell Automation 5094-IA16
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 5094-UM001E-EN-P - April 2020 193
Safety Data for I/O Modules Appendix D
FLEX 5000 I/O Safety
Output Module Safety Data
Tab le 69 lists the safety data for the 5094-OB16S and 5094-OB16SXT modules.
Table 69 - 5094-OB16S and 5094-OB16SXT Digital Safety Parameter Data
Attribute
Point Operation Type
Single Channel Dual Channel
Total Failure Rate (λ (safety related)) 2.0565E-06 2.5524E-06
Safe Failure Fraction (SFF) 99.977% 99.983%
Safe Failure Rate (λS) 1.3238E-06 1.5666E-06
Safe Detected Failure Rate (λSD) 1.32E-06 1.57E-06
Safe Undetected Failure Rate (λSU) 8.40E-10 6.86E-10
Diagnostic Coverage (DC) 99.937% 99.956%
Dangerous Failure Rate (λD) 7.3278E-07 9.8585E-07
Dangerous Detected Failure Rate (λDD) 7.3232E-07 9.8541E-07
Dangerous Undetected Failure Rate (λDU) 4.6523E-10 4.3173E-10
Diagnostic Test Interval (hours) 4 4
Hardware Fault Tolerance (HFT) 0 1
Spurious Trip Rate (STR) 5.68E-06
Mean Time to Failure, Spurious (MTTF-spurious), (hours) 176037
PFH (1/hours) 4.6523E-10 4.3173E-10
PFD
AVE
, at Mission Time of 20 years 4.0754E-05 3.7819E-05
Safety Reaction Time (SRT), (millisecond) 4.5 4.5