4-12 Programming
1560D-UM051D-EN-P – February 2005
Advanced Setup While the Basic Setup group allows the user to get started with a minimum
number of parameters to modify, the Advanced Setup group allows full
access to the SMC Dialog Plus™ controller's powerful parameter set.
Following is a listing of the additional setup parameters provided.
Note: All of the Basic Setup parameters are available in the Advanced
Setup group. The parameters shown below are in addition to the
parameters in Basic Setup.
Parameter Option
Dual Ramp X
Allows the user the option to choose between two Soft Start
profiles.
Off, On
Ramp Time #2
Determines the soft start time for the second ramp of the
Dual Ramp feature.
0 to 30 seconds
Initial Torque #2
Provides the initial torque setting for the second ramp of the
Dual Ramp feature.
0 to 90% locked rotor torque
Undervoltage Level [
Determines the trip level as a percentage of line voltage.
0 to 99% (0 is the Off setting)
Undervoltage Delay [
Provides a delay period prior to a trip occurrence.
0 to 99 seconds
Overvoltage Level
Determines the trip level as a percentage of line voltage.
0 to 199% (0 is the Off setting)
Overvoltage Delay Y
Provides a delay period prior to a trip occurrence.
0 to 999% (0 is the Off setting)
Jam Level Z
Determines the trip level as a percentage of the motor’s full
load current.
0 to 999% (0 is the Off setting)
Jam Delay
Provides a delay period prior to a trip occurrence.
0.0 to 10.0 seconds
Unbalance Level
Allows the user to set the voltage unbalance trip level.
0 to 25% (0 is the Off setting)
Unbalance Delay Y
Provides a delay period prior to a trip occurrence
0 to 99 seconds
Rebalance
Off (not used in MV Dialog Plus)
Underload Level Y
Determines the trip level as a percentage of the motor’s full
load current.
0 to 99% (0 is the Off setting)
Underload Delay
Provides a delay period prior to a trip occurrence.
0 to 99 seconds
X The Dual Ramp feature is available only with the standard controller.
Y The delay time must be set to a value greater than zero when Overvoltage or Unbalance are enabled.
Z For Jam and Underload detection to function, the Motor FLC must be programmed in the Calibration
group. See Chapter 5 for instructions.
[ For Medium Voltage applications, the Undervoltage Level should be set to 80%, and the Undervoltage
Delay should be zero.