Rockwell Automation Publication 2099-UM001G-EN-P - December 2022 183
Appendix C
Upgrade Firmware
This appendix provides procedures for using the ControlFLASH™ utility to
upgrade the firmware in a Kinetix® 7000 drive.
Before You Begin
Upgrading the firmware of a Kinetix 7000 servo drive using the ControlFLASH
utility involves entering the name of the target device, locating the Sercos
interface module and Kinetix 7000 servo drive to be flashed, finding the existing
new firmware levels, and flashing the drive firmware.
Before you begin this procedure, make sure you have the following.
Topic Page
Before You Begin 183
Upgrade Firmware 184
Description Catalog Numbers Version
RSLogix 5000®Software 9324-RLD300NE 15.0 or later
RSLinx® Software 0355-RSLETENE 2.50.00 or later
ControlFLASH Kit N/A 4.00.09 or later
Firmware for Logix Sercos interface module or
PCI card
1756-MxxSE 15.32 or later
1756-L60M03SE 15.4 or later
1768-M04SE 15.35 or later
1784-PM16SE 15.33 or later
Firmware upgrade file for Kinetix 7000
(1),(2)
(1) Contact Rockwell Automation Technical Support at (440) 646-5800 for firmware upgrade files and assistance.
(2) Go to rok.auto/support
for firmware upgrades.