30 Programming Manual SATEL
Note: In the LCD keypad, the ENTRY DELAY, DELAY ACTIVATION TIME and WAITING TIME
parameters are programmed as the ALARM DELAY.
Arm mode – the armed mode activated after violating a zone with the reaction type
13. ARM/DISARM or 14. ARMING. You can select either fully arming, day arming or night
arming.
Detector – type of detector and the method of its connection (zone configuration):
no detector – no detector is connected to the zone;
NC – the zone supports a detector of NC (normally closed) type;
NO – the zone supports a detector of NO (normally open) type;
EOL – the zone supports a NO or NC detector in EOL configuration;
2EOL/NO – the zone supports a NO detector in 2EOL configuration;
2EOL/NC – the zone supports a NC detector in 2EOL configuration;
roller – the zone supports a roller shutter detector;
vibration – the zone supports a vibration detector.
Note: In case of the VIBRATION configuration, opening the circuit for 200 ms – irrespective of
the programmed number of pulses and sensitivity (see below) – will be interpreted as
violation. This solution enables a magnetic detector to be connected in series with the
vibration detector.
Sensitivity – depending on selected zone configuration:
– NO, NC, EOL and 2EOL – the time during which the zone must be violated, so that it
can be noted by the control panel. The sensitivity is programmed in milliseconds.
Values from the 20 ms to 5100 ms range can be entered.
– Vibration – the pulse whose duration is equal to or longer than the defined time will
cause violation of the zone. Values from the 3 ms to 96 ms range can be programmed
(every 3 ms).
Pulse validity – the time counted from the pulse occurrence during which subsequent pulses
must occur (their number being defined as the PULSE COUNT) so that the zone is violated.
The following values can be programmed: 30 ms, 120 ms, 240 ms and 0. If no further
pulses will occur within the defined time period, the pulse counter will be reset. The pulse
counter is reset automatically at arming/disarming. If the value 0 is programmed, the
counter will only be reset at arming/disarming. This parameter is programmed for the
ROLLER configuration.
Pulse count – the number of pulses after which the zone will be violated. This parameter is
programmed for the ROLLER and VIBRATION configuration. For the VIBRATION configuration,
it is possible to program values from 0 to 7 (for the value 0, the pulses will not be counted,
the SENSITIVITY parameter only being taken into account). For the ROLLER configuration,
you can program values from 1 to 8.
Note: In the DLOADX program, all the required parameters for zones in ROLLER and
VIBRATION configuration are programmed in the SENSITIVITY field.
Max. violation time – exceeding the maximum violation time is recognized by the control
panel as the detector trouble (e.g. damage or masking). The time is programmed in
seconds and can be up to 255 seconds. Programming the value 0 means that the control
panel will not check the zone for maximum violation time.
Max. no violation time – exceeding the maximum time of no violation is recognized by the
control panel as the detector trouble (e.g. damage or masking). The time is programmed in
hours and can be up to 255 hours. Programming the value 0 means that the control panel
will not check whether the zone is violated or not.