sauter Equitherm - Access to Commissioning Level; View Service Parameters; Change Service Parameters

sauter Equitherm
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EQJW145:
Heating controller
Commissioning
18 7010015003 A
© Fr. Sauter AG
3.2.2 Access to commissioning level
1. Set the upper rotary switch to the Service
position.
2. Press the input knob, select 'In' (=
commissioning)
.
3. Press the input knob.
4. Turn the input knob,
show the code.
5. Press the input knob.
The first SERVice parameter is displayed.
3.2.3 View SERVice parameters
1. Turn the input knob.
2. Select the SERVice parameter you want.
3. Press the input knob.
The value of the parameter is shown.
4. To leave the value unchanged.
5. Press ESC to exit the display.
3.2.4 Change SERVice parameters
Press the ESC key to cancel the operation. The value is not accepted unless
it has already been confirmed.
sec