14 Technical data
14.1 Overview of technical data
Power supply: 230 V
Power supply tolerance:
±
15 %, 50…60 Hz
Power consumption: approx. 2 VA
Type of protection: IP40 (when fitted in panels) (EN 60529)
Protection class: II (EN 60730-1)
Permitted ambient temperature: 0…+50°C
Permitted storage temperature: –25°C…+65°C
Permitted ambient humidity: 5…95 % rH (no condensation)
Conformity
EMC immunity
EN 12098 and CE
EN 61000-6-1, 2
EMC irradiation EN 61000-6-3, 4
Safety EN 60730-1
Weight with base approx. 0.4 kg
Dimensions with base (W
×
H
×
D)
146 x 98 x 58
Time-switch:
Running capacity
Accuracy
Switching period for weekly
programme
Number of switching commands,
weekly programme
Switching period for calendar
programme
Number of switching commands,
calendar programme
Min. 24 hours, after supply was connected
for min. 4 hours. parameters, switching
commands are stored permanently
Better than 1sec/day
10 min
6 / day or 42 / week
1 day
20
Inputs:
5 temperature sensors
1 temperature sensor or remote
control unit
1 binary input/ pulse input
Outputs:
relay output for pumps/pilot timer
6 relays
normally open contact, 230V/2A/cos
> 0.5