EQJW145:
Heating controller
Commissioni
ng
7010015003 A
41
© Fr. Sauter AG
Parameter Description Range Step-
value
CP19 – Device bus: address of EDB 100 digital room operating unit auto, 2…32 1
CP20 0 SMS or MOD bus via modem: automatic configuration of modem
0 = not enabled. 1 = enabled
0…1 1
CP21 5 SMS or MOD BUS via modem: dialling pause in minutes 0...255 1
CP22 5 SMS or MOD BUS via modem: timeout in minutes 1…255 1
CP23 5 SMS or MOD bus via modem: number of dialling attempts 1…255 1
CP24 0 SMS or MOD bus via modem: send message even if error is rectified
0 = not enabled. 1 = enabled
0…1 1
CP25 0 SMS via modem: select language for error message
0 = German.
1 = French.
2 = English.
3 = Italian.
4 = Spanish
0…4 1
CP26 0 MOD bus via modem: disable dialling control station in case of fault
0 = not enabled. 1 = enabled
0…1 1
CP27 0 MOD bus via RS485 or MOD bus via modem: control station commands
expire after control station is inactive for 30 minutes
0 = not enabled. 1 = enabled
0…1 1
Tab. 4: Communication parameters