EasyManua.ls Logo

sauter Equitherm - Fig. 8: EQJW 145 Control Model 1

sauter Equitherm
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EQJW145:
Heating controller
Using
the controller
7010015003 A
85
© Fr. Sauter AG
AB
A
B
UP
LP1
PI
Fig. 8: EQJW 145 control model 1
Weather-compensating flow temperature control (secondary) in converter
installations with priority DHW switching via diverter valve.
Main SERVice parameters (see also 3.3)
SP06 1 (Control model
)
SP13 1 (Return temperature recording enabled)
SP20 120 (Runtime for the 2nd final control element, i.e. the
diverter valve in this case)
SP28 5 (Intervention intensity for violation of limit value for
return temperature
)
SP34 3 (DHW preparation with diverter valve using one DHW
sensor)