EQJW145:
Heating controller
Commissioning
24 7010015003 A
© Fr. Sauter AG
Parameter Description Range Step value
SP49 0 Configurable output
0 = no function
1 = pilot timer function
2 = 2nd tank charge pump (MOD1, 2 only)
3 = forced control of heating medium pump at low
speed in reduced and back-up mode
4 = collective fault alarm
5 = circulating pump
0…5 1
SP50 0 Pump anti-jamming facility
0 = not enabled. 1 = enabled
0…1 1
SP51 25.10 Summer/winter time changeover 01.01 ...
31.12
SP52 25.03 Winter/summer time changeover
SP51 = SP52 means no summer/winter time
changeover
01.01 ...
31.12
SP53 0 Optimisation
0 = not enabled. 1 = enabled
0…1 1
SP60 0 Floor drying
0 = not enabled
7d = functional heating
25°C = ready-for-laying heating
8 = malfunction
9 = successfully completed
0.7d.25°C.8.9 0.7d.25°C.8
.9
Tab. 2: SERVice parameter