EQJW145:
Heating controller
Communication
functions
7010015003 A
77
© Fr. Sauter AG
Display Meaning
EndE
The connection is being disconnected
0FF
It was impossible to reach the provider or the
control station with the permitted number of
dialling attempts (new dialling attempts will be
made on the next day)
Tab. 9: Display for modem operation
6.5 Setting parameters using the PC
Using an additional USB adaptor and the Config-equitherm software, the
EQJW 145 can be configured and parameterised using a PC. To do so, the
adaptor on the EQJW 145 should be connected to the terminals for the
Modbus communication.
Communication type Modbus RTU (CP02 = 2) is set ex works. However, the
address 255 has been set instead of a valid Modbus address in the range
1 - 247. This makes it possible to communicate with the controller using the
EQJW 145 via the Config-equitherm software, without having to set any
communication parameters on the EQJW 145 beforehand.
It is not possible to communicate with non-configured controllers if several
controllers that have not yet been configured are connected to a network. In
such cases, all except one of the controllers that have not yet been
configured have to be switched off first.