21) Max. belt load QMAX = 57 %
Maximum belt load during preselected SPC time
related to nominal belt load.
Time : SPC time, Parameter K 05
Evaluation : SPC time continuously floating
Prerequisite : Totalization ON, V > Vmin
Initialization : Zero at power ON
Max. display : 255 %
22) No load percentage TQ < MIN = 23 %
Total time during which belt load is below Qmin
(F 05), related to SPC time, Parameter K 05
Evaluation : SPC time continuously floating
Prerequisite : Totalization ON, V > Vmin
Initialization : with Q = Qmin at power ON
23) Last taring T (date) 23.51 %
Date and total tare related to nominal belt load
Prerequisites : Correct zero point using taring
program or manual/automatic
zero setting function.
Manual changes of correction
parameters are not recorded.
Displayed are the 5 last taring or zeroing
operations.
24) AO1 = 4.15 mA
Analog output 1 output current
25) AO2 = 10.00 mA
Analog output 2 output current
(on option card)
26) ZE = 53
Pulses output across pulse output of external
totalizing counter, counted from command “Reset
Counter 1 ”
27) ZO = 1
Pulses pending.
If value constantly exceeds zero, pulse frequency
surpasses 10 Hz.
Increase smallest display digit of Counter 1
(Parameter B 07).
28) AI = 12.54 mA
Analog input input current
29) CS = 10851
Check sum of scale software
30) CS_b = 10851
Check sum recomputed in cycles. If value
“CS_b” differs from “CS”, a serious fault is
present. Contact the Schenck Service.
31) BIC-N = 27
Counter reading indicating how often BIC sensor
has been recognized
32) BIC-E = 5
Counter reading indicating faulty BIC circuits not
entered into tare vectors
33) ES-Version = 11
Current EasyServe Version