10 Event Messages
System Messages S
S1 : Memory Error
Program and parameter memories are
checked in cycles. If an error is found, cal is
inoperable in most cases.
Action : Contact the SCHENCK
Service.
Parameter: O02
S2 : No Release
External RELEASE signal pending.
Scale cannot start.
Parameter : O 07
S3 : Maint. STR Meter
Total ON-time of conveyor belt and
measurement is exceeded.
Perform requisite service work, if necessary.
Acknowledgement of message does not
influence time intervals.
Parameters : K 03, K 04
S4 : Maintenance Int. Elec
The INTECONT power supply has been
switched on for a preset period of time.
Perform requisite service work, if necessary.
Acknowledgement of message does not
influence time intervals.
Parameters : K 01, K 02
S7 : Simulation Active
Operating in Simulation mode, scale is not
prepared for normal operation.
The Simulation mode lets you test all scale
functions without material at the time of
commissioning.
Action : Deselect “Simulation” function.
Parameter : N1
S9 : Data Link Host
Serial communication interrupted for longer
than timeout.
Action : Check cable connections.
Parameter : L 03
Electrics E
E1 : Power Failure
Power failed or cut off.
Feed rate possibly not recorded during this
time.
Action : Acknowledge message.
Parameter : O 01
E2 : Namur Err Tacho
Short circuit or breakage in speed transducer
cable. Scale no longer operable.
Action : Check speed transducer cable.
Deselect speed measurement
for a short time using
Parameter B 03 .
Parameter : O 04
E3 : Namur Err Belt
Short circuit or breakage in belt circuit sensor
cable.
Action : Check sensor cable.
Parameter : O 05
E6 : Error Ext. Event
There is an external fault signal.
Actions: Rectify fault.
Parameter: P06 ând O11
0837
INTECONT PLUS VBW
Event Messages
BV-H2214 GB 85