Batching
B1 : Out of Tolerance
Batch not completed with specified accuracy.
Tolerance : Parameters I 04, 05
Event : Parameter I 06
Cause : Automatic adaption started
(Parameter I 03) ?
Material infeed or belt drive
faulty ?
B4: MAX Batch Act. Value
Current batch actual value exceeds preset
tolerance.
Limit value : Parameters I 04, I 08
Signal Lamps
a (green) POWER OK
LED not lit:
1. No power supply
2. Device defective
3. All other functions OK, LED
probably defective. Call display
test.
b (green) CPU OK
Display pending or flashing,
processor system is faulty. Scale is
inoperable.
X (red) ALARM
flashes if an Alarm message is
available.
Display additionally shows event
code.
Action : See relevant event
code.
MIN (red) MIN LIMIT VALUE
lit if feed rate limit value is exceeded
down.
Action : See L1: I<MIN
MAX (red) MAX LIMIT VALUE
lit if feed rate limit value is exceeded
up.
Action : See H1: I>MAX.
No power supply:
Upon short circuit on the secondary side of the power
supply, internal overload protection responds.
Disconnect power supply for approx. 1 minute, and its
is ready to operate again.