Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
SHO (Show Group 1—6 Settings)
Access Levels 1, B, 2
SHOWSET displays the relay settings of the currently selected group. The
entire syntax of the SHO command follows:
SHO n Setting A <Enter>
➤ n specifies the setting group (1 through 6). The default is the
active setting group.
➤ Setting specifies the setting name with which to begin. The
default is the first setting.
➤ If Setting = A, then hidden settings are shown in addition to the
regular settings.
Control characters provide control over the scrolling of the data:
Temporarily Stop Scrolling: <Ctrl+Q> hold down the Control key and
press Q)
Restart Scrolling: <Ctrl+S> (hold down the Control key and press S)
Cancel Scrolling Completely: <Ctrl+X> (hold down the Control key and
press X)
Settings cannot be entered or modified with this command. Change settings
with the SET command from Access Level 2. Refer to Section 6: Setting the
Relay for information on all settings. The following example demonstrates the
report for the SHO command.
=>>SHO <Enter>
Group 1
RID =XFMR 1
TID =STATION A
E87W1 = Y E87W2 = Y E87W3 = Y E87W4 = N
EOC1 = Y EOC2 = Y EOC3 = Y EOC4 = N
EOCC = N
ETHER = Y E49A = N E49B = N
ESLS1 = N ESLS2 = N ESLS3 = N
W1CT = Y W2CT = Y W3CT = Y W4CT = Y
CTR1 = 600 CTR2 = 1200 CTR3 = 2000 CTR4 = 2000
MVA = 100.0 ICOM = Y
W1CTC = 11 W2CTC = 11 W3CTC = 0
VWDG1 = 230.00 VWDG2 = 138.00 VWDG3 = 13.80
TAP1 = 0.42 TAP2 = 2.35 TAP3 = 2.09
O87P = 0.30 SLP1 = 25 SLP2 = 50 IRS1 = 3.0
U87P = 10.0 PCT2 = 15 PCT5 = 35
TH5P = OFF IHBL = N
E32I =0
Press RETURN to continue
50P11P = 4.00 50P11D = 5.00 50P11TC =1
50P12P = OFF
50P13P = 0.10 50P14P = 0.80
51P1P = 0.80 51P1C = U2 51P1TD = 3.00 51P1RS = Y
51P1TC =1
50Q11P = OFF 50Q12P = OFF
51Q1P = 1.20 51Q1C = U2 51Q1TD = 3.00 51Q1RS = Y
51Q1TC =1
50N11P = OFF 50N12P = OFF
51N1P = OFF
DATC1 = 15 PDEM1P = 1.40 QDEM1P = 0.20 NDEM1P = 0.20