7.31
Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
SHO G (Show Global Settings)
Access Levels 1, B, 2
SHOWSET G displays the relay global settings of the currently selected
group. The global settings include Event Report parameters, frequency, phase
rotation, date format, front-panel time-out, the group switching time delay,
DC battery monitor thresholds, breaker monitor settings, analog input labels,
SSn setting group variables, and definition of front-panel programmable LED
and Display Point variables. The syntax of the SHO G command follows:
SHO G Setting <Enter>
➤ Setting specifies the setting name with which to begin. The
default is the first setting.
Settings cannot be entered or modified with this command. Change settings
with the SET G command from Access Level 2. Refer to Section 6: Setting
the Relay for information on all settings. The following example demonstrates
the report for the SHO G command.
=>>SHO G <Enter>
LER = 15 PRE = 4 NFREQ = 60 PHROT = ABC
DATE_F = MDY SCROLD = 2 FP_TO = 16 TGR = 3
TMPREFA = F TMPREFB = F
DC1P = OFF DC2P = OFF DC3P = OFF DC4P = OFF
BKMON1 =TRIP1 + TRIP4
B1COP1 = 10000 B1KAP1 = 1.2
B1COP2 = 160 B1KAP2 = 8.0
B1COP3 = 12 B1KAP3 = 20.0
BKMON2 =TRIP2 + TRIP4
B2COP1 = 10000 B2KAP1 = 1.2
B2COP2 = 160 B2KAP2 = 8.0
B2COP3 = 12 B2KAP3 = 20.0
BKMON3 =TRIP3 + TRIP4
B3COP1 = 10000 B3KAP1 = 1.2
B3COP2 = 160 B3KAP2 = 8.0
B3COP3 = 12 B3KAP3 = 20.0
BKMON4 =0
Press RETURN to continue
ETHRU = N
IAW1 =IAW1
IBW1 =IBW1
ICW1 =ICW1
IAW2 =IAW2
IBW2 =IBW2
ICW2 =ICW2
IAW3 =IAW3
IBW3 =IBW3
ICW3 =ICW3
IAW4 =IAW4
IBW4 =IBW4
ICW4 =ICW4
SS1 =0
SS2 =0
SS3 =0
SS4 =0
Press RETURN to continue
SS5 =0
SS6 =0
LEDA =OCA + 87E1
LEDB =OCB + 87E2
LEDC =OCC + 87E3
DP1 =IN101
DP1_1 =BREAKER 1 CLOSED DP1_0 =BREAKER 1 OPEN
DP2 =IN102
(Continued on next page)