A.5
Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Firmware and Manual Versions
Firmware
Supports PROTO=DNP
SEL-387-5-R406-V0-Z101101-D20001121
SEL-387-6-R401-V0-Z101101-D20001121
Does Not Support PROTO=DNP
SEL-387-5-R306-V0-Z001001-D20001121
SEL-387-6-R301-V0-Z001001-D20001121
SEL-387-5
➤ Corrected A5C0 message to include DNP on DNP versions (applies
to R406 only).
➤ Corrected Event Report formatting error.
➤ Removed 32IOP supervision from REF logic to improve perfor-
mance for fault close to the neutral point.
SEL-387-6
➤ Corrected A5C0 message to include DNP on DNP versions (applies
to R401 only).
➤ Improved THE command output.
➤ Improved thermal element response to measured top-oil values.
➤ Removed 32IOP supervision from REF logic to improve perfor-
mance for fault close to the neutral point.
20001115
Supports PROTO=DNP
SEL-387-6-R400-V0-Z101101-D20000831
Does Not Support PROTO=DNP
SEL-387-6-R300-V0-Z001001-D20000831
➤ Initial version. 20000831
SEL-387-R105-V0-D20000629
➤ Made internal changes to support battery-backed clock hardware
change.
20000630
Supports PROTO=DNP
SEL-387-5-R405-V0-Z101101-D20000621
Does Not Support PROTO=DNP
SEL-387-5-R305-V0-Z001001-D20000621
➤ Created version that supports DNP 3.00 Level 2 Slave protocol.
➤ Added “n” command option to the CHI command. “CHI n” will
now return the last n items contained in the history.
➤ Added DS1302 battery-backed clock support.
➤ Fixed the 50GP setting so it does not accept a violation of: 50Gp-
min 0.05 • Inom • CTRmax/CTR4.
20000621
SEL-387-R104
SEL-387-5-R304-V0-Z001001-D19991029
➤ Manual update only (see Table A.2). 20000203
SEL-387-R104
SEL-387-5-R304-V0-Z001001-D19991029
➤ Manual update only (see Table A.2). 20000128
SEL-387-R104
SEL-387-5-R304-V0-Z001001-D19991029
➤ Manual update only (see Table A.2). 991130
SEL-387-5-R304-V0-Z001001-D19991029
➤ Fixed TID problem.
➤ Fixed OPEN/CLOSE command display error.
➤ Added CID to STA command.
991029
Table A.1 Firmware Revision History—SEL-387-0, -5, -6 Relay (Sheet 4 of 5)
Firmware Identification (FID) Number Summary of Revisions