D.3
Date Code 20170207 Field Reference Guide SEL-734B Capacitor Bank Control
Cable Drawings
Control Cables for Full-Size Enclosures With the Combined Sensor Connector
SEL-C547
Cable SEL-C547 connects to three switches and the control power
transformer (7-pin female connectors).
J1
Phase 1
Phase 2
Phase 3
Power Supply
J2
J3
J4
Jacket:
• SOOW Cable
• 6 Conductor, 16 AWG
• Temperature Range:
–40° to 90°C
Industry Approvals:
• UL Flexible Cord UL Subject 62
• CSA Flexible Cord C22.2-49
• MSHA Approved
• RoHS Compliant
• Military Standard
• 3106 Style
• Insert Arrangement 22-14S
• Solid Backshell
• Maximum Diameter: 1.468 inch
• Military Standard
• 3106 Style
• Insert Arrangement 16S-1S
• Solid Backshell
• Maximum Diameter: 1.22 inch
• Shielded SO0W Cable
• UL Standard 62
• UL and CSA Listed
• Temperature Rating: 90°C
• Voltage Rating: 600 V
• 2 Conductor, 12 AWG
Wire Color
Black
White
White
Green
Black
Red
Orange
Blue
White
Green
Black
Red
Orange
Blue
White
Green
Black
Red
Orange
Blue
120 VAC
Neutral
Common
Close
Open
Common
52b
52a
Common
Close
Open
Common
52b
52a
Common
Close
Open
Common
52b
52a
Wire Type
#12 AWG 65/30 Strand
#12 AWG 65/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
#16 AWG 26/30 Strand
Connector Pin
J1-A
J1-B
J1-E
J1-D
J1-C
J1-U
J1-N
J1-M
J1-H
J1-G
J1-F
J1-U
J1-R
J1-P
J1-L
J1-K
J1-J
J1-U
J1-T
J1-S
Connector Pin
Wire Termination
Wire Termination
J2-B
J2-C
J2-D
J2-E
J2-F
J2-G
J3-B
J3-C
J3-D
J3-E
J3-F
J3-G
J4-B
J4-C
J4-D
J4-E
J4-F
J4-G
Function
Power Supply
Phase 1
Phase 2
Phase 3