EasyManua.ls Logo

SEW DRC2 - Page 114

SEW DRC2
212 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
Operating Instructions – Electronic Motor DRC.-..-SNI
8
Description of power section parameters
Parameters
Power section parameters \ display values \ unit status
Status of power
section
index 9702.2
The parameter indicates the status of the power section:
0 = Not ready
1 = Ready, output stage inhibited
2 = Ready, output stage enabled
Drive status
index 9702.7
The parameter indicates the operating state of the power section:
0 = Inhibited
1 = Controller inhibit
•2 = System error
3 = No enable
•6 = Enabled
7 = Rapid stop
8 = Integrator stop
9 = Emergency stop
12 = Pos. operation
15 = Reference travel
Error and error
code index 9702.5
The parameter indicates a pending error with error number in plain text.
Error and suberror
code
index 10071.1
The parameter provides detailed information on the error of an error group.
Error source
index 10404.5
The parameter indicates the error source of a pending error:
•0 = No error
1 = Power section
2 = Command PCB
Operating hours
index 8328.0
The parameter indicates the total number of hours for which the inverter has been
connected to the supply system or an external DC 24 V supply.
Storage cycle every 15 min
Unit: [h]
Enable hours
index 8329.0
The parameter indicates the total number of hours for which the power section was in
ENABLE operating state:
Storage cycle every 15 min
Unit: [h]
Work index 8330.0 The parameter indicates the total of active electrical energy the motor has consumed:
Storage cycle every 15 min
Unit: [kWh]
00
I

Table of Contents