Chapter 6 Operating instructions
S100
34 © SICK AG • Subject to change without notice 8012238/YY30/2015-02-20
6.2 System plug assembly
The system plug has cable entries for cable glands on the underside and on the rear:
system plug SX0B-A0000G for S100 Standard and S100 Professional:
– 1 cable entry with M16 cable gland
– 1 cable entry without M16 cable gland (blanking plug)
– 2 cable entries without M12 cable gland (blanking plugs)
You can also procure the S100 with pre-assembled system plug with varying cable lengths
(see section 6.3 “Pre-assembled system plugs” on page 35 and section 13.3.2 “System
plug S100” on page 64).
The length of the spare cable should be such that the system plug cannot inadvertently
be plugged into a neighbouring S100!
From experience 20 to 30 cm spare cable at the laser scanner have proven to adequate.
In this way you avoid the inadvertent connection of the system plug to a neighbouring
S100 and operation of an S100 with an incorrect configuration. The spare cable enables
you to change the S100 with ease if necessary.
6.2.1 Cable glands
Depending on the application use suitable cable glands on the bottom or rear. For the
CANopen cables you must choose EMC proof cable glands.
Cable gland Cable diameter Usage
M16 (included in the
system plug delivery)
5-9 mm system cables for supply
voltage, outputs, inputs
M16, EMC proof (included
in the S100 delivery)
1)
5-9 mm CANopen
1)
Can be used with the M12 to M16 adapter in the S100 delivery.
Note
Fig. 23: System plug SX0B-
A0000G for S100 Standard
Tab. 7: Use the cable glands
supplied