EasyManua.ls Logo

SICK TRANSIC111LP - Display Product Name and Software Version (Command VERS); Display Status of Submenu Item (Command STATUS); Save Parameters (Command SAVE); Using Memory

SICK TRANSIC111LP
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
8014084/ZWT7/V3-1/2020-06 | SICKOPERATING INSTRUCTIONS | TRANSIC111LP
Subject to change without notice
4 OPERATION
4.15.3 Display status of submenu item (command STATUS)
Displays the settings and status of all submenu items.
Syntax: STATUS<cr>
Example:
4.15.4 Display product name and software version (command VERS)
Displays the device name and software version.
Syntax: VERS<cr>
Example:
4.16 Using memory
4.16.1 Save parameters (command SAVE)
Saves the parameters from RAM to EEPROM.
Syntax: SAVE<cr>
Example:
>status
Submenu items are mode and status:
*** LASER TEMPERATURE CONTROLLER (LTC) ***
Mode : ON
State : TEMP_OK
*** OXYGEN MEASUREMENT (MEA) ***
Mode : MODE2
State : PEAK_LOCKED
Run Time Func.: OFF
*** ANALOG OUTPUT (OUT) ***
Mode : NORMAL
State : NORMAL
*** ERROR CONTROL (ERR) ***
Mode : ON
State : NO ERRORS
*** CUSTOMER INTERFACE (SCI2) ***:
Mode : STOP
*** SERVICE INTERFACE (SCI1) ***:
Mode : STOP
*** DISPLAY BOARD (DB) ***
Mode : NORMAL
State : NORMAL
>
>vers
TRANSIC100LP 9165087 0000 / 1.36>status
NOTICE:
Remember to save parameter changes with the command SAVE so that the changes
are not lost.
>save
EEPROM (basic) saved successfully
EEPROM (op) saved successfully
EEPROM (op_log1) saved successfully
EEPROM (op_log2) saved successfully