EasyManua.ls Logo

Siemens 7SJ82 - Page 1058

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For a transformer, for example, the (primary) value is:
[fo_Idiff-error, 1, en_US]
The I-DIFF unrestrained stage also acts if, for example, due to current-transformer saturation because of a
DC component in the short-circuit current, a 2nd harmonic occurs. The inrush-current detection could inter-
pret this as the closed-circuit current.
The I-DIFF unrestrained protection stage operates both with the fundamental component of the differential
protection and with the instantaneous value.
Metrologically, 2 methods are combined:
Instantaneous-value method
Filter-based method
Instantaneous-Value Method
With the instantaneous-values method, an immediate evaluation of the sampled values of the differential
current i
Diff
(t) occurs. The absolute-value and vector-group adapted currents (i*) are also the basis.
Fundamental-Component Method
Parallel to the instantaneous-value method, the fundamental component works with a temporal delay. Here,
the same measured values are processed as with the I-DIFF method. The fundamental component of the
differential current I
diff
is ordered in the operate curve Figure 7-61 and the trip decision is made.
[dwidffunres-100117-01, 1, en_US]
Figure 7-61 I-DIFF Unrestrained Characteristic Curve
Figure 7-62 shows the overall logic.
Capacitor Bank Protection
7.8 Differential Protection for Capacitor Banks
1058 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals